For direct USB monitoring on Linux, NUT lists usbhid-ups for USB connections to Eaton 5SC and 5P, CyberPower CP1500PFCLCD and select APC Smart-UPS models. If you need live watts, shortlist the Eaton 5SC 750 and 5P 650. Both have device reports with ups.realpower. NUT compatibility list, 5SC 750 report, 5P 650 reports.
What each UPS reports over USB
Each report below shows ups.status, battery.charge, battery.runtime and ups.load. The extra fields come from the named unit’s report. The USB HID driver manual says the amount of data varies by manufacturer and model.
| UPS in the NUT device library | Extra fields in the USB HID report |
|---|---|
| Eaton 5SC 750 | ups.realpower, ups.power, input.frequency |
| Eaton 5P 650 | ups.realpower, ups.power, outlet.1.status, outlet.2.status |
CyberPower CP1500PFCLCD (reports with USB vendor ID 0764 and product ID 0501) | battery.runtime.low, ups.realpower.nominal |
| APC Smart-UPS 1500 (NUT 2.7.2 USB HID report) | battery.temperature, output.frequency, input.transfer.reason |
If those four core fields are enough, all four examples are candidates. Before buying, check the exact model and connection in the compatibility list. For example, the list names APC’s SMT1500I under USB HID, while the table above describes a report labeled Smart-UPS 1500.
Read the telemetry on Linux
This manual example assumes NUT and its usbhid-ups driver are installed, the driver can access one compatible UPS connected by USB, and the upsd data server is configured to listen on localhost. Add this section to ups.conf. usbhid-ups requires the port setting and ignores its value when matching the device. NUT configuration notes, USB HID driver manual.
[myups]
driver = usbhid-ups
port = auto
For a manual setup, start the driver with upsdrvctl start, then start the configured data server with upsd. NUT configuration notes.
Run these read-only commands on the NUT server. The first lists UPS names, the second reads the power status, and the last lists all available fields. Use the name shown by the first command if your section has a different name. NUT upsc manual.
upsc -l
upsc myups@localhost ups.status
upsc myups@localhost
- Power state. Look for
OLon line power.OBmeans on battery andLBmeans low battery. NUT configuration notes. - Battery. Read
battery.chargeas a percentage andbattery.runtimein seconds. NUT variable definitions. - Load. Use
ups.loadfor percent,ups.realpowerfor current watts andups.powerfor current volt-amperes. Treatups.realpower.nominalas nominal watts. NUT variable definitions.
When upsc returns values for your UPS, NUT can read its data. Configure upsmon separately for automatic shutdown. For a UPS with an SNMP management card, see the snmp-ups manual. NUT configuration notes.
Evidence and limits. NUT 2.8.5 documentation and historical NUT device reports were checked on November 26, 2026. The commands were not run on hardware for this guide.