Connect the UPS directly to Synology and enable its network UPS server. Set TrueNAS and the Proxmox host up as Network UPS Tools (NUT) clients that monitor the same UPS over the LAN. Put all three hosts on battery-backed power. During the battery test, verify that any switch on either client’s network path to Synology stays powered and that both clients can still read UPS status. The clients need that connection to receive the shutdown signal. BlueWalker setup · NUT configuration manual
Set up Synology as the UPS server
Use a UPS that DSM recognizes. This setup uses a separate TrueNAS machine and a standalone Proxmox VE host. BlueWalker setup · NUT configuration manual
- Connect the UPS to the Synology NAS. In DSM, open Control Panel > Hardware & Power > UPS and select Enable UPS support and Enable network UPS server. DSM integration guide
- Open Permitted Synology NAS Devices and add the LAN IP addresses of TrueNAS and Proxmox. Click OK, then Apply. DSM integration guide · WinNUT Synology setup
- If a firewall sits between the hosts, allow the two client IP addresses to reach the Synology NAS on TCP port
3493. DSM integration guide · NUT protocol guide
Connect Proxmox as a client
Proxmox VE 9.0 uses Debian 13. In the Proxmox host shell, run these commands to install the Debian NUT client. Proxmox VE 9.0 release · APT manual · Debian NUT client manual
apt update
apt install nut-client
Find the UPS name and monitor credentials
Replace synology-ip with the NAS LAN IP address in the examples. List the UPS names, then query the status of the name returned. The example uses ups. A status containing OL means the unit reports line power. upsc manual · NUT configuration manual
upsc -l synology-ip
upsc ups@synology-ip ups.status
Use the UPS monitor username and password accepted by the DSM server. If using the built-in login, consult the credentials listed in the WinNUT project’s Synology instructions. Verify the monitor logins after configuring both clients. WinNUT Synology setup · NUT monitor configuration · NUT protocol guide
Configure the shutdown monitor
Set the mode in /etc/nut/nut.conf to run the network client. nut.conf manual
MODE=netclient
For a host with one power supply backed by the UPS, use the following monitor settings in /etc/nut/upsmon.conf. The example uses NUT’s sample shutdown command. Replace the UPS name, address and credential placeholders with your values. The two 1 values mean the UPS feeds one power supply and the host needs one powered supply. NUT monitor configuration · NUT configuration manual
MONITOR ups@synology-ip:3493 1 MONITOR_USER MONITOR_PASSWORD secondary
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
Enable the monitor at boot and restart it to load the configuration. NUT configuration manual · systemctl manual
systemctl enable nut-monitor.service
systemctl restart nut-monitor.service
Connect TrueNAS as a client
In TrueNAS 25.10, go to System > Services and edit UPS. The 25.10.0 client builds its NUT target from the identifier, remote host and port. It uses the monitor credentials to log in. UPS settings · TrueNAS service code · TrueNAS monitor template
| Setting | Value |
|---|---|
| UPS Mode | Slave, the client mode |
| Identifier | UPS name returned by upsc -l, for example ups |
| Remote Host | Synology LAN IP address |
| Remote Port | 3493 |
| Monitor User and Monitor Password | The same DSM UPS monitor credentials |
| Shutdown Mode | UPS reaches low battery |
| Remote Monitor | Off |
| Power off UPS | Off |
Start UPS on the Services screen and turn on Start Automatically. TrueNAS Services · UPS settings
Verify logins and plan a shutdown test
From Proxmox, check the connected clients for the UPS. For a server that supports client listing, look for both client IP addresses in the output. upsc manual · NUT protocol guide
upsc -c ups@synology-ip
If the server does not support client listing, check the syslog on TrueNAS and Proxmox for upsmon startup messages and errors. If the Synology server logs are available, look for a separate upsd entry for each client IP that includes logged into UPS and the UPS name. A status response or a startup message alone leaves the monitor logins unverified. NUT configuration manual · upsc manual
- If the status query fails, check the DSM allowlist, server address, UPS name and firewall. If status works but a monitor fails to log in, check that client’s credentials and settings. upsc manual · WinNUT Synology setup · NUT configuration manual
- A battery in very poor condition can shut off the UPS immediately. For a controlled outage, switch off the UPS input at the input breaker. A status containing
OBmeans the UPS is on battery. BlueWalker test procedure · NUT configuration manual - Verify that both client hosts shut down before the UPS battery runs out. After restoring input power, verify that each host and UPS monitor returns to service. NUT configuration manual · BlueWalker test procedure
Evidence and limits. The setup follows the DSM integration instructions, TrueNAS 25.10 documentation and source, Proxmox VE 9.0 and Debian 13 manuals for NUT 2.8.1, and the NUT 2.8.5 configuration guide. The steps were not run for this article.